YXZ2V-U, YXZ2V-R, N2XRY

Place of use

These cables have a low dielectric loss, used in indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage. 

Structure

1. Solid or stranded copper conductor.
2. XLPE insulation.
3. Filler.
4. Galvanized round steel wires.
5. Polyester tape.
6. PVC outer sheath. 

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-46000001 3x16+10 23.0 1300 1000 1.15 111 96
28-46000002 3x25+16 27.0 2000 1000 0.727 143 130
28-46000003 3x35+16 29.0 2350 1000 0.524 173 160
28-46000004 3x50+25 32.5 3100 1000 0.387 205 195
28-46000005 3x70+35 38.0 4400 100 0.268 252 247
28-46000006 3x95+50 42.0 5500 500 0.193 303 305
28-46000007 3x120+70 46.5 6850 500 0.153 346 355
28-46000008 3x150+70 51.5 8450 500 0.124 390 407
28-46000009 3x185+95 56.5 10300 250 0.0991 441 469
28-46000010 3x240+120 63.5 12850 250 0.0754 511 551